SPECIFICATIONS |
MODEL |
6303 |
6306 |
6309 |
6315 |
6330 |
6360 |
6390 |
INPUT |
Phase |
1¢ |
3¢ |
Voltage |
230Vac±15% |
220/380Vac±10% |
Frequency |
47-63Hz |
OUTPUT |
Power rating |
Single-Phase Power |
1KVA |
2KVA |
3KVA |
5KVA |
10KVA |
20KVA |
30KVA |
Total Power |
3KVA |
6KVA |
9KVA |
15KVA |
30KVA |
60KVA |
90KVA |
Max. Current (r.m.s) |
0-150V |
8.4A |
16.8A |
25.2A |
42.0A |
84.0A |
168.0A |
252.0A |
0-300V |
4.2A |
8.4A |
12.6A |
21.0A |
42.0A |
84.0A |
126.0A |
Phase |
3¢/4W |
Waveform Distortion |
< 1% at 45-500Hz (Resistive Load) |
Crest Factor |
> 3 |
Line to Phase Regulation |
± (0.5% of output +0.5V) at Resistive Load |
Line to Line Regulation |
± (1% of output +1V) at Resistive Load |
Deviation of phase angle |
120° < ±1° at Load Balance, 120° < ±2.5° at 100% Load Unbalance |
Response Time |
< 2 msec |
SETTINGS |
Voltage |
PhaseRange |
0-150V/0-300V Selectable |
Resolution |
0.1V |
Accuracy |
±(1% of setting + 2counts) |
Frequency |
Range |
45-500Hz FullRange Adjust |
Resolution |
0.1Hz at 45-99.9Hz , 1Hz at 100-500Hz |
Accuracy |
±0.02% of setting |
MEASUREMENT |
Voltage |
PhaseRange |
0.0-300.0V |
LineRange |
0.0-520.0V |
Resolution |
0.1V |
Accuracy |
± (1% of reading + 2counts) |
Frequency |
Range |
0.0-500.0Hz |
Resolution |
0.1Hz |
Accuracy |
±0.1Hz |
Current (r.m.s) |
Range |
L |
0.000-3.500A |
0.00-35.00A |
H |
3.00-35.00A |
30.00-350.0A |
Resolution |
L |
0.001A |
0.01A |
H |
0.01A |
0.1A |
Accuracy |
L |
± (1% of reading +5counts) |
± (1% of reading +2counts) |
H |
± (1% of reading +1count) |
± (1% of reading +1count) |
Power |
Range |
L |
0.0-350.0W |
0.000-3.500KW |
H |
300-4000W |
3.00-40.00KW |
Resolution |
L |
0.1W |
0.001KW |
H |
1W |
0.01KW |
Accuracy |
L |
± (1.5% of reading +5counts) |
± (1.5% of reading +5counts) |
H |
± (1.5% of reading +1count) |
± (1.5% of reading +1count) |
Power Factor |
Range |
0.000-1.000 |
Resolution |
0.001 |
Accuracy |
Calculated and displayed to three significant digits |
GENERAL |
PLC Remote |
I/P:ON/OFF, P1, P2, P3, O/P:Processing |
Memory |
8 Memoies, 5steps per memory for Voltage, Frequency, Test Time, Delay time and Current, Power, Power Factor Hi, Lo Limit setting. |
Timer |
0=Continuous, 1-9999. (Unit: sec, minute, hour selectable) |
Auto Loop Cycle |
0=Continuous, OFF=Loop Once, 2~9999. (Unit:×1, ×10, ×100) |
Auto Voltage Adjust |
Enable it for improve voltage regulation within ±0.1V |
Efficiency |
≧80%(at Full Load ) |
≧85%(at Full Load ) |
Protection |
Over Load , Short Circuit , Over Temperature |
Calibration |
Front Panel Calibration |
Interface (Option) |
GPIB/RS232 |
Environment |
0-40℃/20-80%RH |
Dimension (W×H×D) mm |
430×729 ×650, 14U |
430×729 ×650, 14U |
600×818 ×900, 16U |
600×818 ×900, 16U |
600×952 ×900, 19U |
600×1390 ×900, 28U |
900×1725 ×1200, 35U |
Net Weight |
105Kg |
120Kg |
222Kg |
290Kg |
460Kg |
760Kg |
1200Kg |
product specifications are subject to change without notice. |